The RTC70.XX is used for 2-position control with on/off output for the control the temperature by means of an NTC sensor
Introduction
The RTC85.XX is used for 2-position control with on/off output for the control the temperature by means of an NTC sensor placed externally or internally in the thermostat
The thermostat acquires the actual temperature with its built-in sensor or floor sensor, and the heating contact will close when the room temperature falls below the selected setpoint
Application
For the control of warm-water (floor) heating systems and direct electric
heating systems used in Commercial buildings, Residential buildings, Light
industrial buildings...
Features
LED indicator is light when heating is on
With manual switch and knob for easy operation
On/off control output for heating device
Setback function when connecting with a programmable timer (RTC70.33&RTC70.36)
Temperature limitation function for protecting the floor (RTC70.33&RTC70.36)
Technical data
Voltage : AC230V (AC110V / AC24V available)
Power consumption : 5W
Setting range : +4'C~+45'C
Limitation scale : +25'C~+50'C (RTC70.33&RTC70.36)
Setback temperature : +5'C (RTC70.33&RTC70.36)
Switching differential : ±0.5K
Ambient temperature : -5'C~+50'C
Protective housing : IP20
Housing material : self-extinguishing PC
Floor sensor : rubber-thermoplastic NTC sensor, cable length is 3m
Selection table:
Model No.
Current
Sensor
Temperature limitation functionSetback function
Loading (PCS/Carton)
RTC70.13
3A
Built-in sensor
No
No
64
RTC70.16
16A
Built-in sensor
No
No
64RTC70.2616AFloor sensorNoNo64RTC70.333ABuilt-in & floor sensor (optional)YesYes64RTC70.3616ABuilt-in & floor sensor (recommend)YesYes64